Product Page URL | View |
Cross Radius | 0.0573 ft |
Cross to Cap Base Length | 0.0677 ft |
Cap Radius | 0.0625 ft |
Application | The Wilkins Model ZW1017 Aqua-Gard Tempering Mixing Valve, when installed at the hot water source, is designed to mix hot and cold water in order to reduce the temperature of the hot water in the distribution system to 122°F(50°C) or less. The ZW1017's superior accuracy ensures safe water temperature from minimum to maximum flow rate. Further, multiple end configurations make this valve suitable for all residential and most light commercial installations. WARNING: This device should never be installed at the point of use where the end user could change its setting. Point of use device must be of the ASSE 1016 variety. It is recommended that the ZW1017 be installed with a shut-off valve and thermometer in the tempered water line to provide accurate and safe water mixing temperatures, to be used in conjunction with ASSE 1016 device |
Weight | 2 |
Description | Wilkins Model ZW1017 Aqua-Gard Tempering Mixing Valve, designed to mix hot and cold water in order to reduce the temperature of the hot water in distribution system to 122°F or less |
Temperature Hot Supply Range | 120-195°F |
URL | View |
Body Base to Cross Length | 0.2813 ft |
Product Install & Maintenance Sheet URL | View |
Cross Length | 0.4375 ft |
Manufacturer | Zurn Wilkins |
Standards Compliance | ASSE, CSA |
Model | 12-ZW1017 |
Product data url | View |
Temperature Cold Supply Range | 40-75°F |
Output Temp. Range | 95-131°F |
Assembly Code | D2020300 |
Specification Sheet URL | View |